| PRODUCT > SET (HIGHTVOLT EQUIPMENT) > LIVE PART INSULATOR > DROP OUT FUSE CUTOUT COVERS ................................................................................................................................................................................. |
|
INSULATION COVERS FOR DROPOUT FUSE CUTOUT | |
|---|---|
|
|
|
| Material (วัสดุ) : The live part insulation covers made of polyethylene compound and have UV radiation resistantand tracking resistant properties. grey color |
|
Product Feature - The insulation covers for dropout fuse cutout for covering upper live part of fuse cutout to prevent short circuit from animals or tree touching. - The insulation covers for dropout fuse cutout easy to install and not be fallen while operating the fuse cutout - The insulation covers for dropout fuse cutout designed to prohibit birds enter and make a nest inside. - The insulation covers suitable for fuse cutout product which installed in PEA's Referent Standard PEA Specification IEC 60695-11-10:2013 Fire hazard testing -Part 11-10: Test flames IEC 60243-1:2013 Electric strength of insulating materials-Test methods-Part1 ASTM D 638-03 Standard test method for tensile Properties of plastics |
| GUARANTEE PERFORMANCE DATA OF LIVE PART INSULATION COVERS | ||
| Live part insulation cover type | For dropout fuse cutout | |
| Manufacturer's name | S.ELECTRIC.CO.,LTD. | |
| Country of origin | THAILAND | |
| Type/Model/Catalogue No. | 190250040 | |
| RATING : | ||
| Material : Polyethylene compound or Rubber compound | - | Polyethylene compound |
| Rated power frequency withstand voltage, dry - (1 minute) for complete unit |
kV,rms | 40 kV.rms, 1 min (passed) |
| Tensile strength : before heat aging test | kgf/mm2 | 1.48 kgf/mm2 |
| Tensile strength : after heat aging test | kgf/mm2 | 1.48 kgf/mm2 |
| Elongation : before heat aging test | % | 458.4% (avg.) |
| Elongation : after heat aging test | % | 460% (avg.) |
| Dielectric withstand voltage : before weathering resistance test |
kV/mm | 10 kV/mm. (withstood) |
| Dielectric withstand voltage : after weathering resistance test |
kV/mm | 10 kV/mm. (withstood) |
| Flammability : According to IEC 60695-11-10 | Yes/No | Yes, Class HB (passed) |
| Color of insulation covers : black or grey or red | - | Grey |